Adopted Codes & Construction/Design Requirements

All new construction and remodel construction shall conform to the 2012 International Fire Code, 2012 International Building Code, and the Utah State Fire Marshal's Laws, Rules, and Regulations.

Fire Alarm systems shall be designed to most recent NFPA 72 and USU campus standards. The USU Campus Standard for Fire Alarms is available online. Click here to view the USU Campus Standard for Fire Alarms.

The fire sprinkler system shall be designed and installed to most recent NFPA 13 and USU campus standards.

Commercial Kitchen Hood systems shall be listed to UL 300 and designed and installed per most recent NFPA 96 standards.

All Fire Hydrants and fire mains shall be installed per most recent NFPA 24 standards.

All Standpipe systems shall be designed and installed per most recent NFPA 14 standards.

All fire pumps shall be designed and installed per most recent NFPA 20 standards.

In case of conflicting code requirements, the most restrictive code shall apply. NFPA standards shall be enforced when not addressed by the IFC or the IBC.

All projects shall have construction documents drawn up and reviewed by USU Campus Planning and/or the USU Fire Marshal's office.

Other requirements for new construction:

CHECKLIST:

for plan submittals to the Fire Marshal office:

  • Three (3) sets of all required plans shall be submitted to the Fire Marshals office for review. A set of reviewed and stamped plans shall be kept at the job site for inspection references.
  • The required plans shall consist of the following, along with the name, address and telephone number of the architect, contractor, and person responsible for the project-
  •  
  • SIGHT PLANS:
    • Topography information
    • Access roadways for fire apparatus
    • Property setbacks
    • Building footprints with location on property, and separation from existing buildings
    • All existing and proposed hydrants within 600' of structure
    • Engineer's water supply analysis
    • Hydrant and fire main details, with sizes, depths and backfilling instructions
  • CONSTRUCTION PLANS:
    • Details on size, height, construction type, occupancy rating, calculated occupancy loads, and any anticipated fire protection features
    • Construction plans with information on construction type, construction materials, fire-proofing, flame spread, and all fire and life safety considerations
  • FIRE PROTECTION PLANS:
    • Sprinkler shop drawings with cut sheets
    • Fire alarm shop drawings with cut sheets

 

Plans that are reviewed and approved shall be stamped and signed by the fire marshal. One set shall be retained by the fire marshals office, and one set shall be maintained at the construction site for inspection purposes.

FIRE APPARATUS ACCESS ROADS:

  1. Exterior walls and any portion of said walls, which are more than 150 feet from the curb line of the public street, shall be served by a fire apparatus access road which shall be totally unobstructed. This distance shall me measured by an approved route around the exterior of the building or facility. Access ways may be required on 2 sides, three sides, and the distance from the fire engine to any access point on a wall shall not exceed 150 feet.
  2. All access roads shall be of an all weather surface, defined as concrete or asphalt, capable of supporting the imposed loads of fire apparatus. Fire apparatus roads shall have an unobstructed width of not less than 20 feet, and are subject to required signs and/or road striping and curb painting to maintain this width where parking or turning radius may pose a problem. A schematic of the recommended turning radius is available to download in .jpg format: click here to download .jpg file.
  3. The minimum acceptable vertical clearance shall be 13 feet 6 inches.
  4. The maximum grade permissible shall be 6%.
  5. Any building over 30 feet in height, measured from the lowest level of fire apparatus access, shall have an access road with a minimum unobstructed width of 26 feet, in a zone parallel to the building, no nearer than 15 feet nor further than 30 feet from the building.
  6. Any dead end access road in excess of 150 feet shall be provided with an approved turnaround. The approved turnaround may be configured as a circle, tee, hammerhead, or other functional design.

NOTE: Construction documents for proposed fire apparatus access and locations of fire lanes shall be submitted to the Fire Marshal office for review and approval prior to construction. Required fire apparatus access roads shall be constructed and in service prior to and maintained during construction.

WATER SUPPLY:

  1. A water supply analysis shall be performed by a qualified engineer and fire flows shall be verified by an engineer, and a report shall be provided by the architect.
  2. Fire flow requirements for proposed construction shall be based upon Appendix B of the 2006 International Fire Code.
  3. Fire Hydrants shall be provided along the required fire apparatus access roads and adjacent public streets.
  4. The minimum number of fire hydrants required, spacing, and maximum distance street to hydrant shall be based on appendix C of the International Fire Code.
  5. Fire hydrant mains shall be no smaller than 8 inches, and shall avoid dead end situations so that the required fire flow is not compromised.
  6. Hydrants shall be approved dry barrel type having two 2 1/2 inch outlets and one 4 1/2 inch steamer connection, all outlets having NST (National Standard Threads).
  7. The Fire Marshal is permitted to allow a 50% reduction in the required fire flow for all buildings that are fully sprinklered.
  8. Where fire hydrants are subject to impact by motor vehicles, they shall be protected by guard posts, as specified in section 312 of the International Fire Code.

NOTE: Construction documents and hydraulic calculations for fire hydrant systems shall be submitted to the Fire Marshal office for review and approval prior to construction. Any and all hydrants required for the proposed construction shall be installed and in service prior to construction, and shall be maintained during the construction phase.

FIRE SPRINKLER SYSTEMS:

  1. Automatic sprinkler systems shall be designed to meet the latest adopted edition of NFPA 13, Standard for the Installation of Sprinkler Systems.
  2. The sprinkler system demand for water supply shall not be greater than 90% of the available water supply at peak demand.
  3. The fire protection main shall be at least 6 inches, and shall not be smaller than the sprinkler riser.
  4. All sprinkler systems shall be hydraulically calculated.
  5. Fire sprinkler plan submittals shall be accompanied by cut sheets.
  6. The USU Campus Standard for Fire Sprinkler Systems is available online. Click here to view the USU Campus Standard for Fire Suppression.
  7. The USU Campus Standard for Back Flow Preventer is downloadable in .pdf format: click here to download .pdf file.

NOTE: All documents required must be submitted, reviewed, and approved by the USU Fire Marshal's office. After changes are made and approved, submit fire sprinkler plans to the Utah State Fire Marshal's Office for review prior to starting the installation process.

FIRE ALARM SYSTEMS:

  1. Fire alarm systems shall be designed to meet the requirements of the latest edition of NFPA 72.
  2. The requirements of NFPA 72 are deemed sufficient to meet the requirements of the ADA.
  3. The USU Campus Standard for Fire Alarms is available online. Click here to view the USU Campus Standard for Fire Alarms.
  4. Alarm shop drawing submittals shall be accompanied by cut sheets on all devices proposed.
  5. All devices used shall be UL listed, or listed by a nationally recognized testing lab, and compatible with Notifier panels.
  6. All fire alarm panels shall be Notifier panels.
  7. All stairway doors in protected stair enclosures shall be equipped with a magnetic door holder which is tied into the fire alarm system in buildings equipped with a fire alarm system.

NOTE: All documents required must be submitted, reviewed, and approved by the USU Fire Marshal's office. After changes are made and approved, submit fire alarm plans to the Utah State Fire Marshal's Office for review prior to starting the installation process.

ADDITIONAL REQUIREMENTS:

  1. Hi Rise Buildings: Building of B rated occupancies exceeding 75 feet in height from the lowest fire apparatus access as specified in the IBC, or those not meeting access as necessary for Aerial Fire Apparatus are classified as HI RISE buildings, and must meet the requirements IBC 509,907.2.12.
  2. Fire extinquishers have been standardized to Amerex 456. Fire extinguisher cabinets shall be recessed or semi-flush mounting with no locking mechanism.
  3. Back up generators serving fire and life safety features shall be listed to UL 2200.

 

#theTemplate.getDirectEidtLink()#